SPEC |
Brand | Zircon |
Model | 1000VA 500W |
Input |
Voltage
| 220 VAC +/-25% |
Frequency | 50Hz. +/-10% |
Output |
Voltage | 220 VAC +/-10%(AVR), +/-5%(Battery) |
Frequency | 50Hz. +/-0.1% |
Wave Form | Sine Wave In Normal Condition Modified Sine Wave In Backup Condition |
System Protection |
System Design
| Line Interactive UPS with Stabilizer, Microprocessor Control |
Transfer Time | Typical 4-6 ms.
|
Surge Energy Dissipation | 320 Joules (6500A)
|
Noise Filter | EMI Suppression |
Overload & Short Circuit | Reset Fuse Protection |
Battery |
Type
| Maintenance Free Sealed Lead-acid Battery
|
Battery | 12V 7.8Ah |
Recharge Time
| 4-6 Hours (90% After Fully Discharged)
|
Backup Time | Backup Time 15-30 Min. (Depend on loads) |
Indicator |
LCD Display | Normal, Battery, Battery Low, Battery Replace, Charge, UPS Fault |
Environment |
Ambient Temperature
| -10 to +40 ºC |
Audible Noise | < 45db(1 Meter)
|
Relative Humidity | 95% (Non-Condensing)
|
Safety | IEC/EN62040-1;IEC/EN60950-1 |
Electromagnetic | IEC/EN62040-2;IEC61000-4-2;IEC61000-4-3;IEC61000-4-4;IEC61000-4-5; |
Compatibility | IEC61000-4-6;IEC61000-4-8 |
Standard |
Regular Approvals | TISI1291:2553, 2555, ISO9001:2015, ISO14001, CE, FCC, RoHS |
Dimensions | 101 x 291 x 143 mm. |
Weight | 4.5kg. |